6-9

MULTI STEP FREQUENCIES

(Relationship between the terminals and multi-step frequency 1 to 7)

s

00

20

21

22

23

24

25

26

Multi-step

Frequency

Analog

Digital

Speed

1

Speed

2

Speed

3

Speed

4

Speed

5

Speed

6

Speed

7

X1 – CM

OFF

ON

OFF

ON

OFF

ON

OFF

ON

X2 – CM

OFF

OFF

ON

ON

OFF

OFF

ON

ON

X3 – CM

OFF

OFF

OFF

OFF

ON

ON

ON

ON

* 19

DC BRK t

DC INJECTION BRAKING TIME "ON"

0.0S

The dc injection brake time is adjustable
from 0.1 to 30.0 seconds using this setting.
A setting of zero (0) causes dc braking to be
inactive.

CAUTION:

Use care when applying dc braking as motor

currents & temperatures can build up to very high levels in
a short period of time possibly resulting in motor damage.

Seven (7) digitally preset speeds can be programmed into Function Codes 20 through 26.
These can be used as part of a pattern operation (see Function Code 65) or individually selectable
through switching of control terminals X1, X2, and X3 (see Function Code 32.)

* 20

MULTI Hz-1

MULTI STEP FREQUENCY #1

0.0

* 21

MULTI Hz-2

MULTI STEP FREQUENCY #2

0.0

* 22

MULTI Hz-3

MULTI STEP FREQUENCY #3

0.0

* 23

MULTI Hz-4

MULTI STEP FREQUENCY #4

0.0

* 24

MULTI Hz-5

MULTI STEP FREQUENCY #5

0.0

* 25

MULTI Hz-6

MULTI STEP FREQUENCY #6

0.0

* 26

MULTI Hz-7

MULTI STEP FREQUENCY #7

0.0

Brake Start
Frequency

Brake
Voltage

Brake
Time

Output

Voltage

Output

Frequency

Advertising