GE Industrial Solutions AF-300E$ User Manual

Page 79

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-22

FREQUENCY CONTROL

These Function Codes are used to avoid the
natural mechanical vibration of the load.
The three jump frequencies can be set
independently and are adjustable from 0 to
400 Hz.

53

JUMP Hz-1

FREQUENCY JUMP SETTING

0

54

JUMP Hz-2

FREQUENCY JUMP SETTING

0

55

JUMP Hz-3

FREQUENCY JUMP SETTING

0

56

JUMP HYSTR

FREQUENCY JUMP HYSTERESIS

3

This setting determines the hysteresis
(jump width) of the jump frequency setting.
Adjustable from 0 to 30 Hz.

Example: Function Code 53 set at 20 Hz, Function
Code 56 set at 4 Hz. Output frequency will reach
18 Hz, jump to 22 Hz and continue ramping if input
reference is set above 20 Hz. On a decel, output
frequency will reach 22 Hz and jump to 18 then
continue to decel.

Hysteresis

Hysteresis

Jump
Frequency 2

Jump
Frequency1

Output

Frequency

Setting Frequency

t

Jump
Frequency 3

Hysteresis

Advertising