Control terminal board 1⁄2 - 30 hp, Power terminal board – GE Industrial Solutions AF-300E$ User Manual
Page 35
Advertising
4-4
CAUTION
Remove Jumper from between terminals THR and
CM when thermal interlocks are used.
NOTE
Wiring connections for operation with kaypad
reference control.
CM-FWD and CM-THR terminals are jumpered
together at the factory.
✱
Figure 4-4. 1⁄2 - 30 Hp TERMINAL BOARDS
Control Terminal Board 1⁄2 - 30 Hp
FUSES:
Reference UL power circuit
protection requirements.
Refer to Table 4 on page 4-4.
UL Listed non-time delay fuses
should be used.
Power Terminal Board
* Refer to Dynamic Braking Table on Page 4-16.
NOTE: P1 - P+ terminals are jumpered together at the factory.