GE Industrial Solutions AF-300E$ User Manual

Page 58

Advertising
background image

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION

SETTING

6-1

00

FREQ COMND

FREQUENCY COMMAND

0

Frequency reference can be supplied by
three different methods: Keypad
(digital), 0 to +10 VDC, 4 to 20 mA.

0:

Keypad operation (Digital setting with
/\ or \/ keys).

1:

0 to +10 VDC analog signal (terminal 12),
or a speed potentiometer connected to
terminal 11, 12 and 13.

2:

Sum of 0 to +10 VDC (terminal 12) and 4 to
20 mA (terminal C1).

NOTE : Drives 40HP & greater can use a 0

to + 10 VDC analog signal input (ter-
minal V1) which is summed with the
0 to +10 VDC input.

01

OPR METHOD

OPERATION METHOD

0

RUN, STOP, and RESET commands can be
supplied by two different methods: Keypad
(local) or terminal strip (remote).

0:

Keypad operation (RUN, STOP keys).

1:

Terminal strip operation (Keypad STOP key active).

2:

Terminal strip operation (Keypad STOP key inactive).

NOTE: Remote/local operation can be

toggled by pressing RESET and STOP
keys simultaneously when the
drive is in the STOP condition.

NOTE: Contact between FWD or REV and CM must

be open during power-up or "Er6" trip
will occur.

BASIC FUNCTIONS

NOTE: * = Function can be changed while the Drive is operating.

LCD
GRAPHIC

FACTORY

FUNCTION

DISPLAY

SETTING

DESCRIPTION SETTING

Section 6: Function Code Descriptions