Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 111

Advertising
background image

Logic Functions - Book 1

MODCELL SERIAL COMMUNICATION BLOCK

4-29

26

Default comm switch set (DEFCOMMS)..........................................................................CWR
This diagnostic checks if the default communication switch is set (yes) on the RS-232 or RS-
485 module.

ENABLE

0

Diagnostic error is not suppressed and errors are reported to the
System Event block. The error message is reported as “DEFAULT
COMM SWITCH SET.” This indicates that the default communication
switch is set (yes) on the RS-232 or RS-485 module. Therefore, this
block is functioning as a SLAVE using 9600 baud, no parity and one
stop bit for its communication parameters.

SUPPRESS

1

Diagnostic error is suppressed. Acknowledgement status remains
clear.

27

Default comm Unacked (DEFCOMMU) ........................................................................... – WR
If the default comm switch set diagnostic is enabled, this status indicates if the diagnostic is or
is not unacknowledged. The status can be acknowledged or read as follows.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

28

Default comm Active (DEFCOMMA) ................................................................................– – R
If the default comm switch set diagnostic is enabled, this status indicates if the diagnostic is or
is not active. The status can be read as follows.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

30

I/O Module Mismatch (MODMM).......................................................................................– – R
If the module missing or invalid diagnostic is suppressed, this status indicates if the diagnostic
is or is not active (unsuppressed form of I/O module mismatch active). The unsuppressed
mismatch condition is used to determine if there is an active mismatch condition when
switching the diagnostic from suppress to enable. The status can be read as follows.

NO

0

Diagnostic error is active.

YES

1

Diagnostic error is not active.

31

Board Number (BOARD) ...................................................................................................– – R
This is the board number that is configured for the physical module. Currently, the only valid
value is one.

32

Slot Number (SLOT) ..........................................................................................................– – R
This is the slot number that is configured for the physical module. The valid values are 32 for
occurrence one; 30 or 29 for occurrence two; and 28, 27, or 26 for occurrence three.

33

Message Check Counter (MSGCHKC) ............................................................................ – WR

34

Parity Error Counter (PARC)............................................................................................ – WR

35

Break Error Counter (BRKC)............................................................................................ – WR

36

Framing Error Counter (FRAMEC) .................................................................................. – WR

37

Noise Error Counter (NOISEC) ........................................................................................ – WR

38

Overrun Error Counter (ORUNC) .................................................................................... – WR

39

Invalid Message Counter (INVMSGC) ............................................................................. – WR

40

Receive Buffer Full Counter (RFULLC)........................................................................... – WR

Advertising