Logic 3, regulatory 2, batch 1 functionality, Logic 2, regulatory 1 functionality, Logic 1 functionality – Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 244

Advertising
background image

Logic Functions - Book 1

APPENDIX A - VERSION DIFFERENCES

A-2

A.4

LOGIC 3, REGULATORY 2, BATCH 1 FUNCTIONALITY

These instrument versions have a Version 1 MSC Block (renamed from Modbus Slave to
Modcell Serial with version 2 of the block). The version 1 block does not include attributes 26
to 28 and 83 to 88 and does not include event code 14. This functionality is used to support
communication modules with the address switch and support Extended Modbus, Modbus
master (see Appendix B) and slave communications.

A.5

LOGIC 2, REGULATORY 1 FUNCTIONALITY

These instrument versions do not include the following I/O module and function blocks:

NM

Notification/Request Message Block

SM

Supervisory Message Block

ML

Modbus List Block

MSC

Modbus Slave Communication Block

In addition, the Version 1 Expression Block does not include the following operators:

**

Raise to the power

ABS

Absolute value

EXP

Exponential

NLOG Natural Log
LOG

Log (base 10)

INT

Integer

IF, THEN, and ELSE Conditional Operators

A.6

LOGIC 1 FUNCTIONALITY

The Version 1 instrument does not include the following I/O module and function blocks:

RIM

Resistance Input Module

WRIM Wide Resistance Input Module

RI

Resistance Input Block

RTI

RTD Input Block

RTTI

RTD Transmitter Input Block

In addition, configuration choices for RTD type linearizations are not included in the following
Version 1 blocks (the version attribute for these blocks changed to version 2):

LN

Linearization Block (Linearization Type attribute does not include options for
platinum and nickel RTD sensors)

VCIM

Voltage/Current Input Module (was Thermocouple Type short state attribute 21,
TCTYPE, and is now Linearization Type long state attribute 28, TYPE)

TIM

Thermocouple Input Module (Cold Junction Compensation attribute does not
include options for NONE, RIM and WRIM)

TI

Thermocouple Input Block (Cold Junction Compensation Input attribute does not
exist)

Advertising