Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 116

Advertising
background image

Logic Functions - Book 1

MODCELL SERIAL COMMUNICATION BLOCK

4-34

87

Write Message Action

(WRACT) ...................................................................................... CWR

This value indicates the action that will be taken if a message times out.

NO

0

Discard message and return NAK code “TIME EXPIRED MSG
DISCARDED”

YES

1

Return NAK code “TIME EXPIRED MSG PROCESSED”. The
message will be processed when it can but it may or may not be
accepted.

88

Foreground List (FG) ........................................................................................................C – R
Connect a Configured List block (LISTOUT) to the FGLISTIN connection of this block to
specify foreground data (FG value = occurrence number of the CL block). This data will also
be included in any interface files you build for this port at compile time. In Logic Controller
versions 1 - 4, Regulatory Controller versions 1 - 3, and Batch Controller version 1, foreground
data can't exceed 246 bytes (when packed). In all other MODCELL versions, foreground data
can't exceed 2400 bytes (when packed).

NONE

0

Indicates there is no list attached.

10-4096 Occurrence number of the configured list block

Background List

To allow a host PC access to background attributes, the Application Builder allows for a
connection from a configured list block (LISTOUT) to the BGLISTIN for this block. This data
will also be included in any interface files built for this port at compile time.

Advertising