Logic Functions - Book 1

ANALOG INPUT MODULE BLOCKS (VCIM, TIM, RIM, WRIM)

5-41

VCIM 12

Unacked Input Module Error (VCIMERRU)..................................................................... – WR

TIM 12

Unacked Input Module Error (TIMERRU) ....................................................................... – WR

RIM 12

Unacked Input Module Error (RIMERRU) ....................................................................... – WR

WRIM 12

Unacked Input Module Error (WRIMERRU).................................................................... – WR
If the module error diagnostic is enabled, this unacknowledged status indicates if the
diagnostic is or is not acknowledged. The status can be acknowledged or read as follows.

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

VCIM 13

Active Input Module Error (VCIMERRA) ......................................................................... – WR

TIM 13

Active Input Module Error (TIMERRA) ............................................................................ – WR

RIM 13

Active Input Module Error (RIMERRA)............................................................................ – WR

WRIM 13

Active Input Module Error (WRIMERRA) ........................................................................ – WR
If the module error diagnostic is enabled, the active status indicates if the error is active even
after acknowledgement. The status can be read as follows.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.

14

I/O Module Mismatch (MODMM).......................................................................................– – R
Even though the I/O mismatch diagnostic may be suppressed and its value not stored with the
active I/O mismatch attribute, the actual I/O mismatch condition is still determined. This
unsuppressed I/O mismatch is used to determine if an I/O mismatch exists when changing the
I/O mismatch diagnostic from suppressed to enabled.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.

15

Board number (BOARD)....................................................................................................– – R
This is the board number that the physical module is configured for. Currently, the only valid
value is 1.

16

Slot number (SLOT)...........................................................................................................– – R
This is the slot number that the physical module is configured for. Valid values are 1 to 32 for
the VCIM, TIM, and RIM and 1 to 16 for the WRIM.

17

Module id (MODID) ............................................................................................................– – R
The module id is read as part of the initialization process. This value is compared with the
configured block type to determine if there is a module mismatch.

Advertising