Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 233

Advertising
background image

Logic Functions - Book 1

ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)

7-23

04

Diagnostic Group Supp. (SUPPGRP) ..............................................................................CWR
The diagnostic error reported by this block can be grouped for System Event block control of
its reporting. The selections are:

NONE

No group assigned.

1 to 7

Defines the diagnostic group number for the diagnostic suppression group

controlled by the System Event block.

05

Diagnostic Error (CERRS) ................................................................................................CWR
When a calculation error (calculation overflow or divide by zero) is detected, the block
completes the calculation using some reasonable value (+ or - maximum value for overflows
and divide by zero), reports the diagnostic error as “CALCULATION ERROR”, and sets the
output quality bad if Set quality bad on calculation error? is YES. The diagnostic error will
clear and the quality will be set back to good when a subsequent execution of the block
performs a successful calculation.

ENABLED

0

Calculation error is enabled.

SUPPRESSED 1

Calculation error is suppressed.

06

Calc. Error Unacked (CERRU) ......................................................................................... – WR
If the calculation error diagnostic is enabled, the unacknowledged status indicates if the
diagnostic is or is not acknowledged. Only writeable in DEBUG.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

07

Calc. Error Unacked Quality (CERRUQ) ......................................................................... – WR
If the calculation error diagnostic is enabled, this status indicates if the quality of the
unacknowledged diagnostic is GOOD or BAD. Only writeable in DEBUG.

OOD

0

Quality when the loop block is RUN or HOLD.

BAD

1

Quality when the loop block is OFF.

08

Calc. Error Active (CERRA) ............................................................................................. – WR
If the calculation error diagnostic is enabled, the active status indicates if the diagnostic is
active even after acknowledgement. Only writeable in DEBUG.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

09

Calc. Error Active Quality (CERRAQ) ............................................................................. – WR
If the calculation error diagnostic is enabled, this status indicates if the quality of the active
diagnostic is GOOD or BAD. Only writeable in DEBUG.

GOOD

0

Quality when the loop block is RUN or HOLD.

BAD

1

Quality when the loop block is OFF.

10

Set quality bad on calculation error? (SETQBAD) .........................................................CWR
The result quality can be affected by a calculation error as follows.

NO

0

Result quality is not affected by a calculation error.

YES

1

Quality is set BAD when a calculation error occurs.

Advertising