Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 195

Advertising
background image

Logic Functions - Book 1

REMOTE DIGITAL INPUT MODULE BLOCK (RDIM)

6-17

00

Version (VERSION)

– – R

Version number of RDIM block. Presently 1.

01

Block Length (BLKLEN).....................................................................................................– – R
Number of database bytes used.

02

State (STATE).....................................................................................................................– – R
Not configurable in this block (always equal to RUN). See Section 2.4.1, State Changes for
additional information. This block, when configured, is always executed in the RUN state
(Normal Operation).

03

Bad Inputs Accepted (BADINP) ........................................................................................– – R
This block does not check on input quality. This attribute is set at YES (1) and is not
configurable.

04

Diagnostic Group (SUPPGRP) .........................................................................................CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.

NONE

No group assigned.

1 to 7

Defines the diagnostic group number for the diagnostic suppression group

controlled by the System Event block.

05

I/O Mismatch (MODMMS) ..................................................................................................CWR
The I/O mismatch diagnostic compares each CS-31 bus address configured for a remote
digital I/O module against the content of the address during a power-up or data base
download. If the address is not used or the installed module does not match the configuration,
this diagnostic is generated.

SUPPRESS

1

Diagnostic error is suppressed. Acknowledgement status remains
clear. Even though the I/O mismatch diagnostic is suppressed, the
actual I/O mismatch condition is still determined (see Attribute 11,
MODMM).

ENABLE

0

Diagnostic error is not suppressed and errors are reported to the
System Event block. The error message is reported as I/O
MISMATCH

06

Unacknowledged I/O Mismatch (MODMMU) .................................................................. – WR
If the I/O mismatch diagnostic error is enabled, the unacknowledged I/O mismatch diagnostic
status indicates if the diagnostic is or is not acknowledged. The status can be acknowledged
or read as follows.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

07

Active I/O Mismatch (MODMMA) ..................................................................................... – WR
If the I/O mismatch diagnostic error is enabled, the active I/O mismatch diagnostic status
indicates if the error is active even after acknowledgement. The status can be read as follows.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

Advertising