Logic Functions - Book 1

DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)

5-20

DOM 09

Unacked DOM Module Error (DOMERRU) ......................................................................– WR

DDOM 09

Unacked DDOM1 Module Error (DDOERRU1) ................................................................– WR

DDOM 12

Unacked DDOM2 Module Error (DDOERRU2) ................................................................– WR

WDOM 09

Unacked WDOM Module Error (WDOMERRU) ...............................................................– WR
If this diagnostic error is enabled, the unacknowledged DO module diagnostic status indicates
if the diagnostic is or is not acknowledged. The status can be acknowledged or read as
follows.

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

DOM 10

Active DOM Module Error (DOMERRA)........................................................................... – – R

DDOM 10

Active DDOM1 Module Error (DDOERRA1) .................................................................... – – R

DDOM 13

Active DDOM2 Module Error (DDOERRA2) .................................................................... – – R

WDOM 10

Active WDOM Module Error (WDOMERRA) .................................................................... – – R
If this diagnostic error is enabled, the active DO module diagnostic status indicates if the error
is active even after acknowledgement. The status can be read as follows.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.

DOM 11

I/O Module Mismatch (MODMM) ...................................................................................... – – R

DDOM 14

I/O Module Mismatch (MODMM) ...................................................................................... – – R

WDOM 11

I/O Module Mismatch (MODMM) ...................................................................................... – – R
Even though the I/O mismatch diagnostic may be suppressed and its value not stored with the
active I/O mismatch attribute, the actual I/O mismatch condition can still be determined by this
attribute (value is unsuppressed). This attribute is used to determine if there is an I/O
mismatch when changing the I/O mismatch diagnostic from suppressed to enabled.

YES

1

Diagnostic error is active.

NO

0

Diagnostic error is not active.

DOM 12

Board Number (BOARD) ................................................................................................... – – R

DDOM 15

Board Number (BOARD) ................................................................................................... – – R

WDOM 12

Board Number (BOARD) ................................................................................................... – – R
This is the board number that the physical module is configured for. Currently, the only valid
value is one.

DOM 13

Slot Number (SLOT) .......................................................................................................... – – R

DDOM 16

Slot Number (SLOT) .......................................................................................................... – – R

WDOM 13

Slot Number (SLOT) .......................................................................................................... – – R
This is the first slot number that the physical module is configured for. The valid values are 1
to 32 for DOM modules and 1 to 13, 15, 17, or 19 to 31 for DDOM and WDOM modules.

DOM 14

Action (ACTION) ................................................................................................................ CWR

DDOM 17

Action (ACTION1) .............................................................................................................. CWR

DDOM 27

Action (ACTION2) .............................................................................................................. CWR

WDOM 14

Action (ACTION) ................................................................................................................ CWR
The action is applied to the result before being sent to the output module and it is applied to
the output again to get the readback value.

REVERSE

0

The result is inverted before being sent to the output module.

DIRECT

1

The result is sent to the output module without change.