Logic Functions - Book 1

ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)

7-15

Table 7-4. Resistance Input Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Version

VERSION

1

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

State

STATE

RUN(0), HOLD(1), OFF(2),
DEBUG(3)

CWR Short State

02

Bad Inputs Accepted

BADINP

NO (0), YES (1)

CWR Discrete

03

Diagnostic Group Supp.

SUPPGRP

NONE, 1, 2, 3, 4, 5, 6, 7

CWR Long State

04

Calculation Error

CERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Calc. Error Unacked

CERRU

NO (0), YES (1)

– WR Discrete

06

Calc. Error Unacked Quality

CERRUQ

GOOD (0), BAD (1)

– WR Discrete

07

Calc. Error Active

CERRA

NO (0), YES (1)

– WR Discrete

08

Calc. Error Active Quality

CERRAQ

GOOD (0), BAD (1)

– WR Discrete

09

Set quality bad on calc err?

SETQBAD

NO (0), YES (1)

CWR Discrete

10

Action

ACTION

REVERSE (0), DIRECT (1)

CWR Discrete

11

Filter Type

FILTYPE

NONE(0), AUTO(1), USER(2)

CWR Short State

12

Filter Time

FILTIME

0 to 1000 (minutes)

CWR Floating Pt

13

Output Range - Top

OUTHI

value (in scaled units)

CWR Floating Pt

14

Output Range - Bottom

OUTLO

value (in scaled units)

CWR Floating Pt

15

Quality Limit - Top

QUALHI

value (in scaled units)

CWR Floating Pt

16

Quality Limit - Bottom

QUALLO

value (in scaled units)

CWR Floating Pt

17

Initial Value (

Result)

R

value (in scaled units)

CWR Floating Pt

18

Result Data Quality

RQ

GOOD (0), BAD (1)

– WR Discrete

19

Advertising