Logic Functions - Book 1

REMOTE DIGITAL OUTPUT MODULE BLOCK (RDOM)

6-30

31-46

Extended Error, Channel 0 (EXTERR0) through Channel 15 (EXTERR15) .....................– WR
The last error code as read from the remote module (whether active or not). See packed
extended errors PKDERRS attribute 244. Codes are as follows:

0

No Error

1

Internal error in remote unit

2

Cut wire (open circuit)

4

Overload + open circuit

6

Overload + open circuit

8

Short circuit

10

Short Circuit +open circuit

12

Overload + short circuit

14

Short circuit + overload + open circuit

15

Remote module not present

16

No remote I/O present

47 - 62

Mode, Channel 0 (MODE0) through Channel 15 (MODE15) ............................................. CWR
The mode of the block is determined by configuring and/or writing this attribute. Switching
mode is a reportable block event.

MAN

0

The block output is the result value, which can be written by the user.

AUTO

1

The block output is processed using the input data.

63 - 78

Action, Channel 0 (ACTION0) through Channel 15 (ACTION15)...................................... CWR
The action is applied to the result before being sent to the remote output module.

REVERSE

0

The result is inverted before being sent to the output module.

DIRECT

1

The result is sent to the output module without change.

79 - 94

Restart Output, Channel 0 (RSOUT0) through Channel 15 (RSOUT15).......................... CWR
If a cold or frozen start up is occurring, the result will be set depending upon the selection
made here.

FALSE

0

TRUE

1

95 - 110

CPU Failsafe Output,Channel 0 (FSOUT0) through Channel 15 (FSOUT15) .................. CWR
This is the output value used when communication between the instrument CPU and the
remote I/O interface module is lost. A write to the failsafe output value causes the value to be
downloaded to the module.

FALSE

0

Failsafe output value is low.

TRUE

1

Failsafe output value is high.

PREVIOUS

3

The last value output by the RIO module.