INTERFACE BLOCK

3-14

23

Memory module is soft write protected Active (MDSWPACT)...................................... – – R
The write protect bit in the module RAM has been set by software.

YES

1

“MEMORY MODULE IS SOFT WRITE PROTECTED” is active.

NO

0

Diagnostic error is not active.

24

Instrument is overconfigured (OVRUNSUP) .................................................................. CWR
The “instrument is overconfigured” diagnostic checks if the instrument is able to complete all
of its tasks at the intervals specified. The diagnostic can be suppressed or enabled as follows:

SUPPRESS

1

Diagnostic error is suppressed.

ENABLE

0

Diagnostic error is enabled.

25

Instrument is overconfigured Unacknowledged (OVRUNUAK)....................................– WR
The unacknowledged instrument is overconfigured diagnostic indicates if the condition is or is
not acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

26

Instrument is overconfigured Active (OVRUNACT)....................................................... – – R
The instrument is unable to complete all of its tasks at the intervals specified. The scan
execution times should be examined to determine which tasks should be simplified or run at a
slower rate or items should be moved to another task. Note that when the instrument is
overconfigured, all tasks will run at a proportionally slower rate. This may be a temporary
condition if instrument is getting too many messages. You should not ignore this condition if it

is persistent.

YES

1

“INSTRUMENT IS OVERCONFIGURED” is active.

NO

0

Diagnostic error is not active.

27

Instrument powered up (PWRUPSUP) ............................................................................ CWR
The instrument powered up diagnostic checks if the instrument went through power up. The
diagnostic can be suppressed or enabled as follows:

SUPPRESS

1

Diagnostic error is suppressed.

ENABLE

0

Diagnostic error is enabled.

28

Instrument powered up Unacknowledged (PWRUPUAK) .............................................– WR
The unacknowledged instrument powered up diagnostic indicates if the condition is or is not
acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

29

Instrument powered up Active (PWRUPACT) ................................................................ – – R
The instrument went through power up. A time stamp indicating the time power was restored
is entered in the event queue.

YES

1

“INSTRUMENT POWERED UP” is active.

NO

0

Diagnostic error is not active.