Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 206

Advertising
background image

Logic Functions - Book 1

REMOTE DIGITAL OUTPUT MODULE BLOCK (RDOM)

6-28

03

Bad Inputs Accepted (BADINP) ....................................................................................... – – R
This attribute is present but is not used in this block. See attributes 15 through 30.

04

Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.

NONE

No group assigned.

1 to 7

Defines the diagnostic group number for the diagnostic suppression group

controlled by the System Event block.

05

I/O Mismatch (MODMMS) ................................................................................................. CWR
The I/O mismatch diagnostic compares each CS-31 bus address configured for a remote
digital I/O module against the content of the address during a power-up or data base
download. If the address is not used or the installed module does not match the configuration,
this diagnostic is generated.

SUPPRESS

1

Diagnostic error is suppressed. Acknowledgement status remains
clear. Even though the I/O mismatch diagnostic is suppressed, the
actual I/O mismatch condition is still determined (see Attribute 11,
MODMM).

ENABLE

0

Diagnostic error is not suppressed and errors are reported to the
System Event block. The error message is reported as I/O
MISMATCH

06

Unacknowledged I/O Mismatch (MODMMU)...................................................................– WR
If the I/O mismatch diagnostic error is enabled, the unacknowledged I/O mismatch diagnostic
status indicates if the diagnostic is or is not acknowledged. The status can be acknowledged
or read as follows.

NO

0

Diagnostic error is acknowledged.

YES

1

Diagnostic error is unacknowledged.

07

Active I/O Mismatch (MODMMA)......................................................................................– WR
If the I/O mismatch diagnostic error is enabled, the active I/O mismatch diagnostic status
indicates if the error is active even after acknowledgement. The status can be read as follows.

NO

0

Diagnostic error is not active.

YES

1

Diagnostic error is active.

08

Module Error (EXTERRS) ................................................................................................. CWR
This remote module error diagnostic checks for remote I/O module errors. Reported error
codes are stored in the block database as extended errors (EXTERR, attributes 31-46). The
diagnostic can be suppressed or enabled as follows:

ENABLE

0

Diagnostic error is not suppressed and errors are reported to the
System Event block.

SUPPRESS

1

Diagnostic error is suppressed. Acknowledgement status remains
clear.

Advertising