ANALOG INPUT BLOCKS (VCI, TII, TI, RI, RTI, RTTI)

7-9

Table 7-2. Thermocouple Transmitter Input Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Version

VERSION

1

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

State

STATE

RUN(0), HOLD(1), OFF(2),
DEBUG(3)

CWR Short State

02

Bad Inputs Accepted

BADINP

NO (0), YES (1)

CWR Discrete

03

Diagnostic Group Supp.

SUPPGRP

NONE, 1, 2, 3, 4, 5, 6, 7

CWR Long State

04

Calculation Error

CERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Calc. Error Unacked

CERRU

NO (0), YES (1)

– WR Discrete

06

Calc. Error Unacked Quality

CERRUQ

NO (0), YES (1)

– WR Discrete

07

Calc. Error Active

CERRA

NO (0), YES (1)

– WR Discrete

08

Calc. Error Active Quality

CERRAQ

NO (0), YES (1)

– WR Discrete

09

Set quality bad on
calculation error?

SETQBAD

NO (0), YES (1)

CWR Discrete

10

Action

ACTION

REVERSE (0), DIRECT (1)

CWR Discrete

11

Temperature Scale

SCLTYPE

FAHRENHEIT(0),CELSIUS(1),
RANKINE(2), KELVIN(3)

CWR Short State

12

Filter Type

FILTYPE

NONE(0), AUTO(1), USER(2)

CWR Short State

13

Filter Time

FILTIME

0 to 1000 (minutes)

CWR Floating Pt

14

Transmitter Range - Top

TRANSHI

value (in microvolts)

CWR Floating Pt

15

Transmitter Range - Bottom

TRANSLO

value (in microvolts)

CWR Floating Pt

16

Output Calibrate - Zero

ZERO

value (in temperature units)

CWR Floating Pt

17

Output Calibrate - Span

SPAN

value (multiplier)

CWR Floating Pt

18

Quality Limit - Top

QUALHI

value (in temperature units)

CWR Floating Pt

19

Quality Limit - Bottom

QUALLO

value (in temperature units)

CWR Floating Pt

20

Initial Value (

Result)

R

value (in temperature units)

CWR Floating Pt

21

Result Data Quality

RQ

GOOD (0), BAD (1)

– WR Discrete