Logic Functions - Book 1

DIGITAL OUTPUT MODULE BLOCKS (DOM, DDOM, WDOM)

5-21

DOM 15

Mode (MODE) .....................................................................................................................CWR

DDOM 18

Mode (MODE1) ...................................................................................................................CWR

DDOM 28

Mode (MODE2) ...................................................................................................................CWR

WDOM 15

Mode (MODE) .....................................................................................................................CWR
The mode of the block is determined by configuring and/or writing this attribute. Switching
mode is a reportable event.

MAN

0

The block output is the result value, which may be written by the user.
The readback value is updated with the module value.

AUTO

1

The block output is processed using the input data.

DOM 16

Output to use on restart (RESTART) ...............................................................................CWR

DDOM 19

Output to use on restart (RESTART1) .............................................................................CWR

DDOM 29

Output to use on restart (RESTART2) .............................................................................CWR

WDOM 16

Output to use on restart (RESTART) ...............................................................................CWR
If a cold or frozen start up is occurring, the result will be set depending upon the selection
made here. If this block looses communication with the select circuit, a failsafe condition
results.

PREVIOUS

0

The result existing in the database prior to a failsafe output condition.

PRESET

1

A set value for failsafe output conditions (see preset output value).

DOM 17

Preset Output Value (PRESET) ........................................................................................CWR

DDOM 20

Preset Output Value (PRESET1) ......................................................................................CWR

DDOM 30

Preset Output Value (PRESET2) ......................................................................................CWR

WDOM 17

Preset Output Value (PRESET) ........................................................................................CWR
This is configurable discrete value when preset is selected as the output to use on restart.

FALSE

0

Preset output value is low.

TRUE

1

Preset output value is high.

DOM 18

Failsafe Output Value (FSOUT) ........................................................................................CWR

DDOM 21

Failsafe Output Value (FSOUT1) ......................................................................................CWR

DDOM 31

Failsafe Output Value (FSOUT2) ......................................................................................CWR

WDOM 18

Failsafe Output Value (FSOUT) ........................................................................................CWR
The failsafe output values are stored in the select circuit and are used to determine the output
sent to the module when a failsafe condition occurs. A write to the failsafe output value
causes the value to be downloaded to the module.

FALSE

0

Failsafe output value is low.

TRUE

1

Failsafe output value is high.

FS HOLD

2

Failsafe output value is last result value.

DOM 19

Track Status (TRKSTAT) .................................................................................................. – WR

DDOM 22

Track Status (TRKSTAT1) ................................................................................................ – WR

DDOM 32

Track Status (TRKSTAT2) ................................................................................................ – WR

WDOM 19

Track Status (TRKSTAT) .................................................................................................. – WR
Track status is set to track whenever the path from the input to the result is broken. This
occurs when the data quality is bad, or the I/O lock is locked, or when the mode is manual or
the instrument state is not run.

NO TRACK

0

Data quality is good, I/O lock is unlocked, mode is auto and
instrument state is run.

TRACK

1

Data quality is bad, or I/O lock is locked or mode is manual, or
instrument state is not run.