ANALOG INPUT MODULE BLOCKS (VCIM, TIM, RIM, WRIM)

5-29

Table 5-5. Voltage/Current Input Module Attributes, Valid Values, Mnemonics, and Data Types

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Version

VERSION

1

– – R Long State

00

Block Length

BLKLEN

– – R Count

01

Block State

STATE

RUN (1)

– – R Short State

02

Bad Inputs Accepted

BADINP

YES (1)

– – R Discrete

03

Diagnostic Group

SUPPGRP

NONE, 1 to 7

CWR Long State

04

I/O mismatch

MODMMS

ENABLE (0), SUPPRESS (1)

CWR Discrete

05

Unacked I/O Mismatch

MODMMU

NO (0), YES (1)

– WR Discrete

06

Active I/O Mismatch

MODMMA

NO (0), YES (1)

– WR Discrete

07

I/O communications error

COMMERRS

ENABLE (0), SUPPRESS (1)

CWR Discrete

08

Unacked comm. error

COMMERRU

NO (0), YES (1)

– WR Discrete

09

Active comm. error

COMMERRA

NO (0), YES (1)

– WR Discrete

10

V/I module error

VCIMERRS ENABLE (0), SUPPRESS (1)

CWR Discrete

11

Unacked Input Module Error

VCIMERRU NO (0), YES (1)

– WR Discrete

12

Active Input Module Error

VCIMERRA NO (0), YES (1)

– WR Discrete

13

I/O Module Mismatch

MODMM

FALSE (0), TRUE (1)

– – R Discrete

14

Board number

BOARD

1 through 8

– – R Long State

15

Slot number

SLOT

1 through 32

– – R Long State

16

Module id

MODID

FE0000 = Voltage
FE0100 = Current (passive)
FE0400 = Current (active)

– – R Hex

17

Extended Error Code

EXTERR

0 to 65535

– WR Count

18

Mode

MODE

AUTO (1), MAN (0)

CWR Discrete

19

Input Type

INTYPE

VOLTS (0), MILLIVOLTS (1),
CURRENT (2),
CURRENT 2WIRE (3)

C – R Short State

20

Not used. See Appendix A

21

Signal Range - Top

SIGHI

value in input units

CWR Floating Pt

22

Signal Range - Bottom

SIGLO

value in input units

CWR Floating Pt

23

Initial result

(Result)

R

value

CWR Floating Pt

24

Result Quality

RQ

GOOD (0), BAD (1)

– WR Discrete

25

Field Result

FR

value

– – R Floating Pt

26

Field Result Quality

FRQ

GOOD (0), BAD (1)

– – R Discrete

27

Linearization Type

TYPE

NONE (0), B (1), E (2), J (3), K
(4), N (5), R (6), S (7), T(8),
Platinum, 0.003850 (24),
Platinum, 0.003923 (25),
Platinum, 0.003902 (26),
Platinum, 0.003911 (27),
Nickel, 0.006720 (28)

CWR Long State