Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 45

Advertising
background image

Logic Functions - Book 1

INTERFACE BLOCK

3-19

103

Communication Blocks are Locked Active (CMLOKACT) .............................................– – R
The communications blocks locked active is set when Attribute 158, Lock ICN
Communications Blocks? (COMMLOCK) is YES.

YES

1

“COMMUNICATION BLOCKS ARE LOCKED” is active.

NO

0

Diagnostic error is not active.

104

DMA Unacknowledged (DMAUAK) .................................................................................. – WR
The unacknowledged DMA transfer diagnostic indicates if the condition is or is not
acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

105

DMA Active (DMAACT) ......................................................................................................– – R
The active DMA transfer diagnostic is set when an error occurs in a DMA transfer and the
instrument therefore shuts itself down. The diagnostic is readable when the instrument is
powered up again. See Instrument Shutdown Fault (#036).

YES

1

“DMA FAULT” is active.

NO

0

Diagnostic error is not active.

106

I/O Overrun (IOVRNSUP)...................................................................................................CWR
The I/O overrun diagnostic indicates that the instrument was unable to complete all of its I/O
communications and processing before the data was required by a user task. This error
always forces an INSTRUMENT IS OVERCONFIGURED diagnostic and all tasks will be
scanned at a slower rate so that all the I/O work is completed. The diagnostic can be
suppressed or enabled as follows:

SUPPRESS

1

Diagnostic error is suppressed.

ENABLE

0

Diagnostic error is enabled.

107

I/O Overrun Unacknowledged (IOVRNUAK)................................................................... – WR
The unacknowledged I/O overrun diagnostic indicates if the condition is or is not
acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.

108

I/O Overrun Active (IOVRNACT) .......................................................................................– – R
The instrument is unable to complete all I/O sampling at the intervals specified. The scan
execution times should be examined to determine which tasks should be simplified or run at a
slower rate. Note that when the instrument is overconfigured, all tasks will run at a
proportionally slower rate.

YES

1

“I/O OVERRUN” is active.

NO

0

Diagnostic error is not active.

109

Communication Hardware Fault Unacknowledged (CMHWFUAK) .............................. – WR
The unacknowledged communication hardware fault diagnostic indicates if the condition is or
is not acknowledged. The status can be read or acknowledged as follows:

YES

1

Diagnostic error is unacknowledged.

NO

0

Diagnostic error is acknowledged.