COMMUNICATION MODULE BLOCKS

4-2

The baud rate, data bits, parity, and stop bits that match the device with which you are
communicating can be:

Comm

Type

Link

Baud

Data

Bits

Stop

Bits

Parity

1720N 19200, 9600, 4800, 2400,

1200

8

1, 2

None, Even, Odd

ICN

1731N 19200, 9600

8

1

None

1733N 19200, 9600, 4800, 2400,

1200, 600, 300

8

1

None

Modbus

None

38400,19200, 9600, 4800,
2400, 1200, 600, 300,150

8

1,2

None, Even, Odd

For the ICN module, these parameters are set at the link. For Modbus, the parameters are
configurable through the MSC block.

Production of Interface Files.
A Tagged Interface File (TIF) and a Modcell Interface File (MIF) may be produced for each
communications module (ICN or MSC) in the database. Since up to 3 such modules can
appear in the database, up to 3 TIF’s and up to 3 MIF’s can be produced. The production of
MIF files is not supported in Logic 1 - 4, Regulatory 1 - 3, or Batch 1.