Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) System, I/O and Communications Functions User Manual

Page 90

Advertising
background image

Logic Functions - Book 1

LOOP BLOCK

4-8

Table 4-1. ICN Communication Block Attributes, Valid Values, Mnemonics, and Data Types (Cont’d)

Field Name /

Attribute

Mnemonic

Valid Values

CWR

Data Type

Attr

Bus Restart Counter

RSTC

– WR

Count

34

Restart Failure Counter

FAILC

– WR

Count

35

Invalid Message Counter

MSGC

– WR

Count

36

Check-Sum Error Counter

CRCC

– WR

Count

37

Framing Error Counter

FRAMEC

– WR

Count

38

Noise Error Counter

NOISEC

– WR

Count

39

Overrun Error Counter

ORUNC

– WR

Count

40

Invalid msg. Length Counter

LENC

– WR

Count

41

Receive Buffer Full Counter

RFULLC

– WR

Count

42

Xmit. Buffer Full Counter

XFULLC

– WR

Count

43

Unexp. Comm. Msg. Counter

UCOMMC

– WR

Count

44

ICN Overload Counter

OLOADC

– WR

Count

45

Req. Buffer Full Counter

QFULLC

– WR

Count

46

Foreground List

FG

NONE(0), CL10(10) to CLn

CWR

Count

47

ICN Load

LOAD

– – R

Msec Time

48

Reset Diagnostic Ctrs

RESET

NO (0), YES (1)

– WR

Discrete

49

I/O Module Mismatch

MODMM

NO (0), YES (1)

– – R

Discrete

51

ICN Address

ADDR

ANY, 0 to 15

– – R

Short State

52

Board number

BOARD

1

– – R

Long State

53

Slot number

SLOT

32, 30, 29, 28, 27, 26

– – R

Long State

54

Terminating Source

TERM

FALSE (0), TRUE (1)

– – R

Discrete

55

02

State (STATE) .................................................................................................................... – – R
Not configurable in this block (always equal to RUN). See Section 2.4.1, State Changes for
additional information. This block, when configured, is always executed in the RUN state
(Normal Operation).

03

Bad Inputs Accepted (BADINP) ....................................................................................... – – R
This attribute is not used with this block. The ICN communication block always runs without a
check on input quality. See Section 2.3.2, Data Quality for additional information.

04

Diagnostic Group (SUPPGRP)......................................................................................... CWR
The diagnostic errors reported by this block can be grouped for System Event block control of
their reporting.

NONE

No group assigned.

1 to 7

The number of the diagnostic suppression group as controlled by the System

Event block.

Advertising