7HDFKLQJ3HQGDQW)XQFWLRQDQG6SHFL¿FDWLRQV

20

ƒ Such jog actions with the JOG button are also valid for any not-homed axes. However,

coordinate values in this case have no meaning. Therefore, be extremely careful about
interference with the stroke end.

ƒ If jog operation is performed to the axis in action under the operation-button-acceptable

condition, the operation of the applicable axis is aborted when the JOG operation button is
turned OFF. (The next operation starts, if any.)

18. Deadman switch (*Option)

The Deadman switch has three-level conditions. The ON/OFF in each level is as shown

below.

1st level

Switch OFF

Condition in which the switch is released or a switch pressing
force is too weak

2nd level

Switch ON

Condition in which the switch is pressed by an appropriate
force

3rd level

Switch OFF

Condition in which the switch is pressed by a strong force

In the switch ON condition, servo ON is possible.

In the switch OFF condition, the driver power is cut off and the servo is turned OFF.

Even in the switch OFF condition, operation is possible in the mode not requiring servo ON

(such as the edit mode).

䃁Some controllers such as the X-SEL-K controller display the message shown below when

the power is turned on.

If you press the ESC key, the mode selection screen will be displayed and operation will

become possible in the mode not requiring servo ON even in the switch OFF condition.

䃁When the switch is OFF, the panel window 7-segment LED of the X-SEL-K or KX controller

displays “dsf.”

The panel window 7-segment LED of the X-SEL-P/Q or PX/QX, R/S, RX/SX, RXD/SXD
controller displays “enb.”

ƒ The Deadman switch is valid when the controller’s mode switch is on the MANU side.

ƒ The driver power cannot be cut off regardless of the switch condition when the controller’s

mode switch is on the AUTO side.