3.5 Errorlist / Maintenance Manager

The error list is visible only if an error entry is present. An active entry in the error list is
displayed by a red/green blinking 2nd line and status LED’s in the display.

Err-Status Signification Proceed as follows

2. line
blinks red

existing
error

- determine the error type in the error list via the error number
- remove error

.. is red

error
removed

- Acknowledge the alarm in the error list by pressing key

È

- or

È

- The alarm entry is deleted.

.. is green

no error

All errors can be reset in the function level with

Err

È

rSET (if configured).

3.5.1

Error-List:

Name

Description

Cause

Possible remedial action

E.1 Internal error,

cannot be removed

E.g. defective EEPROM

Contact PMA service

Send- in device

E.2 Internal error, can

be reset

e.g. EMC trouble

-shortly separate the device from
mains supply
- Keep measurement and power
supply cables in separate runs

E.4

Internal error,
option modules

HW-Coding does not
match the current
recognized HW
configuration

- Contact PMA service, send-in
device or check option modules

FBF.
1/2

Sensor break
INP1/2

Sensor defectiveFaulty
cabling

Replace INP1/2 sensor
Check INP1/2 connection

Sht.
1/2

Short circuit
INP1/2

Sensor defectiveFaulty
cabling

Replace INP1/2 sensor
Check INP1/2 connection

POL.1 INP1 polarity error Faulty cabling

Reverse INP1 polarity

HCA

Heating current
alarm

- Heating current circuit

interrupted, I <

HC.A

or I >

HC.A (dependent

of configuration)

- Heater band defective

-Check heating
current circuit

- If necessary, replace
heater band

SSR

Heating current
short circuit

- Current flow in
heating

- Check heating current circuit

- If necessary, replace solid-