9.5 Timer

9.5.1

Setting up the timer

Operating modes

6 different timer modes are available to the user. The relevant timer mode can be set via
parameter SP.Fn in the Conf menu (

r page 27).

Mode 1 (–)
After timer start, control is to the adjusted set-point .
The timer (

t.SP

) runs as soon as the process value

enters or leaves the band around the set-point
(x =

SP

_

b.ti

). After timer elapse, the controller

returns to

Y2

.

End

and the set-point are displayed

alternately in the lower display line.

Mode 2 (····)
Mode 2 corresponds to mode 1, except that control is continued with the relevant set-point
after timer (

t.SP

) elapse.

Mode 3 (–)
After timer start, control is to the adjusted set-point. The
timer (

t.SP

) starts immediately after switch-over. After

timer elapsing the controller switches off. End and the
set-point are displayed alternately in the bottom display
line.
Mode 4 (····)

Mode 4 corresponds to mode 3, except that control is continued with the relevant set-point
after timer (

t.SP

) elapse.

Mode 5 (delay)
The timer starts immediately. The controller output
remains on Y2. After timer (

t.SP

) elapse, control starts

with the adjusted set-point.

Mode 6
After set-point switch-over (

SP

r

SP.2

), control is to

SP.2

. The timer (

t.SP

) starts when the process value

enters the adjusted band around the set-point
(x =

SP.2

_

b.ti

).

After time elapse the controller returns to

SP

. End and

the set-point are displayed alternately in the lower
display line.