Pro-16

23

special 0...4500 Ohm (pre-defined as KTY11-6)

30

0...20mA / 4...20mA Scaling is required (see chp. page 57)

40

0...10V / 2...10V Scaling is required (see chp. page 57)

S.Lin

Linearization (only at S.tYP = 23 (KTY 11-6), 30 (0..20mA)
and 40 (0..10V) adjustable) (see page 74)

0

0 Without

linearization

1

Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The
characteristic for KTY 11-6 temperature sensors is preset.

Corr

Measured value correction / scaling

0

0 Without

scaling

1

Offset correction (at CAL level) (see page 58)

2

2-point correction (at CAL level 58)

3

Scaling (at PArA level) (see page 57)

fAI1

Forcing INP1 (only visible with BlueControl

®

!)

0

0 No

forcing

1

Forcing via serial interface



InP.2

Name

Value range

Description

Default

I.Fnc

Function selection of INP2

1

0

no function (subsequent input data are skipped)

1

heating current input

2 external

set-point

(

SP.E)

5

default correcting variable Y.E (switchover ->

LOGI/ Y.E)

S.tYP

Sensor type selection

31

30

0...20mA / 4...20mA Scaling is required (see chp. page 57)

31

0...50mA AC Scaling is required. (see chp. page 57)

fAI2

Forcing INP2 (only visible with BlueControl

®

!)

0

0 No

forcing

1

Forcing via serial interface