Level – West Control Solutions Pro-16 User Manual

Page 50

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 50 of 88

Pro-16

4.4.5

 - Y - Off controller / 2-point controller with pre-contact

ConF/Cntr: SP.Fn = 0

set-point / cascade controller

C.Fnc = 2

D -Y-Off controller

C.Act = 0

inverse action (e.g. heating applications)

ConF/Out.1: O.Act = 0

action Out.1 direct

Y.1

= 1

control output Y1 active

Y.2

= 0

control output Y2 not active

ConF/Out.2: O.Act = 0

action Out.2 direct

Y.1

= 0

control output Y1 not active

Y.2

= 1

control output Y2 active

PArA/Cntr: Pb1 = 1...9999

proportional band 1 (heating) in units of phys.
quantity (e.g. °C)

ti1

= 0,1...9999

integral time 1 (heating) in sec.

td1

= 0,1...9999

derivative time 1 (heating) in sec.

t1

= 0,4...9999

min. cycle time 1 (heating)

SH

= 0...9999

switching difference

d.SP

= -1999...9999 trigg. point separation suppl. cont.

PArA/SEtP: SP.LO = -1999...9999 D / Y / Off in units of phys. quantity

SP.Hi = -1999...9999 set-point limit low for Weff