4 configuration examples, Level – West Control Solutions Pro-16 User Manual
Page 46
Advertising
Configuration
level
9499-040-93811 / 59537-1
Page 46 of 88
Pro-16
4.4 Configuration examples
4.4.1
On-Off controller / Signaller (inverse)
ConF/Cntr:
SP.Fn
= 0
set-point /cascade controller
C.Fnc
= 0
signaller with one output
C.Act
= 0
inverse output action (e.g. heating applications)
ConF/Out.1: O.Act
= 0
output action Out.1 direct
Y.1
= 1
control output Y1 active
PArA/Cntr:
HYS.L
= 0...9999
switching difference below SP
PArA/Cntr:
HYS.H
= 0...9999
switching difference above SP
PArA/SEtP:
SP.LO
= -1999...9999 lower set-point limit for Weff
SP.Hi
= -1999...9999 upper set-point limit for Weff
g
For direct signaller action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 )
Advertising