4 configuration examples, Level – West Control Solutions Pro-16 User Manual

Page 46

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 46 of 88

Pro-16

4.4 Configuration examples

4.4.1

On-Off controller / Signaller (inverse)

ConF/Cntr:

SP.Fn

= 0

set-point /cascade controller

C.Fnc

= 0

signaller with one output

C.Act

= 0

inverse output action (e.g. heating applications)

ConF/Out.1: O.Act

= 0

output action Out.1 direct

Y.1

= 1

control output Y1 active

PArA/Cntr:

HYS.L

= 0...9999

switching difference below SP

PArA/Cntr:

HYS.H

= 0...9999

switching difference above SP

PArA/SEtP:

SP.LO

= -1999...9999 lower set-point limit for Weff

SP.Hi

= -1999...9999 upper set-point limit for Weff

g

For direct signaller action, the controller action must be changed

(

ConF / Cntr / C.Act = 1 )