West Control Solutions Pro-16 User Manual

Page 21

Advertising
background image

Operation

9499-040-93811 / 59537-1

Page 21 of 88

Pro-16

Start: heating power switched on

Heating power Y is switched off (

1). When the

change of process value X was constant during one
minute (

2), the power is switched on (3).

At the reversal point, the self-tuning attempt is
finished and the new parameter are used for
controlling to set-point W.

Start: heating power switched off

The controller waits 1,5 minutes (

1). Heating

power Y is switched on (

2). At the reversal point,

the self-tuning attempt is finished and control to the
set-point is using the new parameters.

Self-tuning at the set-point

a

The process is controlled to the set-point. With the
control deviation constant during a defined time
(

1), the controller outputs a reduced correcting

variable pulse (max. 20%) (

2). After determination

of the control parameters using the process
characteristic (

3), control is started using the new

parameters (

4).

Three-point controller

a

The parameter for heating and cooling are
determined in two attempts. The heating power is
switched on (

1). Heating parameters Pb1,

ti1, td1 and t1 are determined at the
reversal point. The process is controlled to the set-
point (

2). With constant control deviation, the

controller provides a cooling correcting variable
pulse (

3). After determining its cooling parameters

Pb2, ti2, td2 and t2 (4) from the process
characteristics , control operation is started using
the new parameters (

5).