8 help for manual tuning – West Control Solutions Pro-16 User Manual

Page 22

Advertising
background image

Operation

9499-040-93811 / 59537-1

Page 22 of 88

Pro-16

During phase

3, heating and cooling are done simultaneously!

3-point-stepping controller
After the start (

1) the controller closes the

actuator (

2 Out.2). When the difference

between process value and set-point is big
enough (

3), the changing of the process value

is monitored for 1 min. (

4). Afterwards the

actuator is opened (

5 Out.1). If the reversal

point is reached (

6) or there are made enough

measurements, the parameters are detected
and are adopted.

3.8 Help for manual tuning

The optimization aid should be used with units on which the control parameters shall be
set without self-tuning.

For this, the response of process variable x after a step change of correcting variable y can
be used. Frequently, plotting the complete response curve (0 to 100%) is not possible,
because the process must be kept within defined limits.

Values T

g

and x

max

(step change from 0 to 100 %) or

t and x (partial step response) can

be used to determine the maximum rate of increase v

max

.

y = correcting

variable

Yh = control

range

Tu

=

delay time (s)

Tg

=

recovery time (s)

X

max

=

maximum process value

V

max

=

t

x

Tg

X

Δ

Δ

max

=

= max.

max. rate of increase of process value

The control parameters can be determined from the
values calculated for delay time Tu , maximum rate of
increase v

max

, control range X

h

and characteristic K

according to the formulas given below. Increase Pb, if
stabilized to the set-point oscillates.

Tu

Tg

t

x

y

100%

0%

t

Yh

Xmax

{X

{t

W
X

1min

t

t

1 2 3 4 5 6