Level – West Control Solutions Pro-16 User Manual

Page 47

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 47 of 88

Pro-16

4.4.2

2-point and continuous controller (inverse)

ConF/Cntr SP.Fn

= 0

set-point / cascade controller

C.Fnc

= 1

2-point and continuous controller (PID)

C.Act

= 0

inverse action (e.g. heating applications)

ConF/Out.1: O.Act

= 0

action Out.1 direct

Y.1

= 1

control output Y1 active

ConF/Out.3: O.tYP

= 1 / 2

Out.3 Type ( 0/4 … 20mA)

Out.0

= -1999...9999 scaling analog output 0/4mA

Out.1

= -1999...9999 scaling analog output 20mA

O.Src

= 1

controller output y1 (continuous)

PArA/Cntr: Pb1

= 1...9999

proportional band 1 (heating) in units of phys. quantity
(e.g. °C)

ti1

= 0,1...9999

integral time 1 (heating) in sec.

td1

= 0,1...9999

derivative time 1 (heating) in sec.

t1

= 0,4...9999

min. cycle time 1 (heating)

PArA/SEtP: SP.LO

= -1999...999

set-point limit low for Weff

SP.Hi

= -1999...9999 set-point limit high for Weff

g

For direct controller action, the controller action must be changed

(

ConF / Cntr / C.Act = 1 )