2 boost function, Functions – West Control Solutions Pro-16 User Manual

Page 72

Advertising
background image

Special

functions

9499-040-93811 / 59537-1

Page 72 of 88

Pro-16

9.2 Boost function

The boost function causes temporary increase of the set-point, e.g. for removing "frozen"
material from clogged die nozzles with hot-runner control.

If configured (

r ConF/ LOGI/ booS), the boost function can be started via digital

input di1/2/3, with the function key on the instrument front panel or via the interface
(OPTION).

The set-point increase around boost set-point

PArA /SEtP/SP.bo remains effective

as long as digital signal (di1/2 3, function key, interface) remains set. The maximum
permissible cycle time (boost time-out) is determined by parameter

PArA

/

SEtP/t.bo.

Unless reset after elapse of boost time I

t.bo, the boost function is finished by the

controller.

g

The boost function also works with:

• start-up circuit:

PArA /SEtP/ SP.bo is added to W after elapse of start-up

holding time PArA /SEtP/ t.St.
• Gradient function: set-point W is increased by PArA /SEtP/ SP.bo with gradient PArA
/SEtP/ r.SP.

Advertising