Calibration

level

9499-040-93811 / 59537-1

Page 59 of 88

Pro-16

Offset correction (

ConF/ InP.1 / Corr =1 ):

possible on-line at the process


2-point correction (

ConF/ InP.1 / Corr = 2):


InL.1:

The input value of the lower scaling point is displayed. The operator must

0.0

adjust the lower input value by means of a process value simulator and

confirm the input value by pressing key

Ù

.


OuL.1:

The display value of the lower scaling point is displayed. Before

0.0

calibration,

OuL.1 is equal to InL.1. The operator can correct the

lower display value by pressing the

ÌÈ

keys. Subsequently, he

confirms the display value by pressing key

Щ

.