Configuration

level

9499-040-93811 / 59537-1

Page 27 of 88

Pro-16

Adjustment:

To access the configuration level, press the key

Ù

for 3 seconds and then the key

Ì

to select the ConF-Menu item. Press

Ù

to confirm.

If the password function is activated, a prompt for

PASS is displayed.

The configuration values can be adjusted using the

ÌÈ

keys. Press the

Ù

key to save the value. The next configuration value is shown.

After the last configuration value of a group,

donE is displayed, followed by

automatic changing to the next group

g

Return to the beginning of a group, by pressing the

Ù

key for 3 sec

g

Press menu item

quit to close/cancel configuration


4.2 Configurations

Cntr

Name

Value range Description

Default

SP.Fn

Basic configuration of setpoint processing

0

0

set-point controller can be switched over to external set-point
(->

LOGI/ SP.E

)

1 program

controller

2

timer, mode 1 (bandwidth-controlled, switched off at the end)

3

timer, mode 2 (bandwidth-controlled, set-point remains active
at the end)

4

timer, mode 3 (switched off at the end)

5

timer, mode 4 (set-point remains active at the end)

6

timer, mode 5 (switch-on delay)

7

timer, mode 6 (set-point switch-over)

10

controller with start-up circuit (see page 71)

11

Fixpoint /

SP.E/ SP.2

controller with start-up circuit (see page 71)

b.ti

0…9999 Timer tolerance band

5

C.Fnc

Control behaviour (algorithm)

1

0

on/off controller or signaller with one output

1

PID controller (2-point and continuous)