Level – West Control Solutions Pro-16 User Manual

Page 49

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 49 of 88

Pro-16

4.4.4

3-point stepping controller (relay & relay)

ConF/Cntr: SP.Fn

= 0

set-point / cascade controller

C.Fnc

= 4

3-point stepping controller inverse action (e.g.
heating applications)

C.Act

= 0

action Out.1 direct

ConF/Out.1: O.Act

= 0

control output Y1 active

Y.1

= 1

control output Y2 not active

Y.2

= 0

action Out.2 direct

ConF/Out.2: O.Act

= 0

control output Y1 not active

Y.1

= 0

control output Y2 active

Y.2

= 1

proportional band 1 (heating) in units of phys.
quantity (e.g. °C)

PArA/Cntr: Pb1

= 1...9999

integral time 1 (heating) in sec.

ti1

= 0,1...9999

derivative time 1 (heating) in sec.

td1

= 0,1...9999

min. cycle time 1 (heating)

t1

= 0,4...9999

neutral zone in units of phy. quantity

SH

= 0...9999

min. pulse length in sec.

tP

= 0,1...9999

actuator travel time in sec.

tt

= 3...9999

set-point limit low for Weff

PArA/SEtP: SP.LO

= -1999...9999

set-point limit high for Weff

SP.Hi

= -1999...9999

set-point / cascade controller

g

For direct action of the 3-point stepping controller, the controller output action
must be changed (

ConF / Cntr / C.Act = 1 )