Level – West Control Solutions Pro-16 User Manual

Page 43

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 43 of 88

Pro-16

short on and off pulses. The shortest pulses result from ¼ x

t1 or ¼ x t2. The

characteristic curve is also called “bath tub curve”.


Parameters to be adjusted

t1 :

min. cycle time 1 (heating) [s]

(

PArA/ Cntr)

t2 :

min. cycle time 2 (cooling) [s]

4.3.4

Switching attitude linear (

CyCl=1)

For heating (

Y1), the standard method (see chapter 4.3.3) is used. For cooling (Y2), a

special algorithm for cooling with water is used.
Generally, cooling is enabled only at an adjustable process temperature (

E.H2O),

because low temperatures prevent evaporation with related cooling, whereby damage to
the plant is avoided. The cooling pulse length is adjustable using parameter

t.on and is

fixed for all output values.
The “off” time is varied dependent of output value. Parameter

t.off is used for

determining the min “off” time. For output of a shorter off pulse, this pulse is suppressed,
i.e. the max. effective cooling output value is calculated according to formula

t.on / ( t.on + t.off) x 100%.


Parameters to be adjusted:

E.H2O: minimum temperature for water cooling

(

PArA / Cntr)

t.on: pulse duration water cooling

t.off: minimum pause water cooling