Input scaling, Scaling – West Control Solutions Pro-16 User Manual

Page 57

Advertising
background image

Input

scaling

9499-040-93811 / 59537-1

Page 57 of 88

Pro-16

6. Input scaling

When using current or voltage signals as input variables for

InP.1 or InP.2,

scaling of input and display values at parameter setting level is required. Specification of
the input value for lower and higher scaling point is in the relevant electrical unit (mA/ V).

Input

Inp.1

g

Parameter

InL.1 , OuL.1, InH.1 und OuH.1 are only visible if

ConF / InP.1 / Corr = 3 is chosen.

S.tYP Input

signal

InL.1 OuL.1 InH.1 OuH.1

30

(0...20mA)

0 … 20 mA DC

0 -1999...9999 20 -1999...9999

4 … 20 mA DC

4 -1999...9999 20 -1999...9999

40

(0...10V)

0 … 10 V

0 -1999...9999 10 -1999...9999

2 … 10 V

2 -1999...9999 10 -1999...9999


In addition to these settings,

InL.1 and InH.1 can be adjusted in the range

(0...20mA / 0...10V) determined by selection of

S.tYP .

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings of

InL.1 and OuL.1 as well as of

InH.1 and OuH.1 must correspond.

Input

InP.2

S.tYP

Input signal

InL.2 OuL2 InH.2 OuH.2

30

0 … 20 mA DC

0 -1999...9999 20 -1999...9999

31

0 … 50 mA AC

0 -1999...9999 50 -1999...9999

In addition to these settings,

InL.2 and InH.2 can be adjusted in the range

(0...20/ 50mA) determined by selection of

S.tYP.