7 self-tuning – West Control Solutions Pro-16 User Manual

Page 15

Advertising
background image

Operation

9499-040-93811 / 59537-1

Page 15 of 88

Pro-16

3.7 Self-tuning

(automatic adaption of control parameters)
For determination of optimum process parameters, self-tuning is possible.
After starting by the operator, the controller makes an adaptation attempt, whereby
the process characteristics are used to calculate the parameters for fast line-out
to the set-point without overshoot.

The following parameters are optimized when self-tuning:

Parameter set 1:

Pb1 Proportional band 1 (heating) in engineering units [e.g. °C]
ti1 Integral time 1 (heating) in [s] r only, unless set to OFF
td1 Derivative time 1 (heating) in [s] r only, unless set to OFF
t1

Minimum cycle time 1 (heating) in [s]. This parameter is optimized only, unless
parameter Cntr/Adt0 was configured for “no self-tuning” using BlueControl

®

Pb2 Proportional band 2 (cooling) in engineering units [e.g. °C]
ti2 Integral time 2 (cooling) in [s] r only, unless set to OFF
td2 Derivative time 2 (cooling) in [s] r only, unless set to OFF
t2

Minimum cycle time 2 (cooling) in [s]. This parameter is optimized only, unless
parameter Cntr/Adt0 was configured for “no self-tuning”using BlueControl

®

Parameterset 2: according to Parameterset 1 (see page 23)

3.7.1

Preparation before self-tuning

o

The limits of the control range must be adjusted for the controller operating range, i.e.
rnG.L and rnG.H must be adjusted to the limits within which control must take
place Configuration

rControllerrspan start and end of control range)

ConFrCntrrrnG.L and rnG.H

o

Determine which parameter set must be optimized.
- The currently effective parameter set is optimized.
r activate the corresponding parameter set (1 or 2).

o

Determine which parameter must be optimized (see the list given above)

o

Select the method for self-tuning (See Chapter 3.7.616)
- Step attempt after start-up
- Pulse attempt after start-up
- Optimization at the set-point