Programmer
9499-040-93811 / 59537-1
Page 70 of 88
Pro-16
Start by setting the bandwidth high and low (
b.Lo; b.Hi
) limits and the control output
reset value (
d.00
) for the selected program. The bandwidth is valid for all.
g
Configuration parameter
pCom (r page 40) can be used for display suppression of
bandwidth parameters and control output reset value, which, however, remains
valid.
Select the segment number (
SEg; Segm.-No) for the segment which is to be edited.
Now, enter segment type, segment end set-point, segment time/gradient and control
output.
After confirming parameter
d.Out with key
Ù
, select the following segment.
Copying a program
The procedure for copying a program is shown below.
When confirming function
COPY with key
Ù
, the program which shall be copied must
be selected (
Src). Subsequently, the target program (dSt) must be adjusted. Press key
Ù
to start copying.