Parameter adjustment effects

Parameter Control

Stabilized of disturbances

Start-up behaviour

Pb1

higher increased damping slower stabilized

slower reduction of duty cycle

lower reduced damping

faster stabilized

faster reduction of duty cycle

td1

higher reduced damping

faster response to disturbances faster reduction of duty cycle

lower increased damping slower response to disturbances slower reduction of duty cycle

ti1

higher increased damping slower stabilized

slower reduction of duty cycle

lower reduced damping

faster stabilized

faster reduction of duty cycle

Formulas

K = Vmax * Tu

With 2-point and 3-point
controllers, the cycle time must
be adjusted to
t1 / t2 ß 0,25 * Tu

controller behaviour

Pb

[phys. units]

td

[s]

ti

[s]

PID

1,7 * K

2 * Tu

2 * Tu

PD

0,5 * K

Tu

OFF

PI

2,6 * K

OFF

6 * Tu

P

K

OFF OFF

3-point-stepping

1,7 * K

Tu

2 * Tu


3.9 Second PID parameter set

The process characteristic is frequently affected by various factors such as process value,
correcting variable and material differences.
To comply with these requirements, the controller can be switched over between two
parameter sets. Parameter sets

PArA and PAr.2 are provided for heating and cooling.


Dependent of configuration, switch-over to the second parameter set
(

ConF/LOG/Pid.2) is via key

è

, one of digital inputs di1…di4

or interface (OPTION).

g

Self-tuning is always done using the active parameter set, i.e. the second
parameter set must be active for optimizing.