Operation

9499-040-93811 / 59537-1

Page 25 of 88

Pro-16

The following variables are available (

ConF / Lim / Src .x ):

Variable (

Src .x) Remark

Alarm type

Process value

Absolute

Control deviation xw

Process value - effective set-point. The effective
set-point Weff is used. E.g with a ramp, this is the
changing set-point rather than the target set-point.

Relative

Control deviation xw +
suppression after start-
up or set-point change
with time limit

The alarm output is suppressed after switch-on or
after a set-point change, until the process value is
within the limits for the first time. At the latest
after elapse of time 10 x

ti1 the alarm is

activated (

ti1 = integral time 1; parameter r

Cntr). If ti1 is switched off (ti1 = OFF),
this is considered as Î , i.e. the alarm is not
activated before the process value was within the
limits once.

Relative

Effective set-point
Weff

The effective set-point Weff for control.

Absolute

Correcting variable y

y = controller output signal

Absolute

Deviation from SP
internal

Process value - internal set-point. The internal set-
point is used. E.g. with a ramp, this is the target
set-point instead of the varying effective set-point
Weff.

Relative

Control deviation xw +
suppression after start-
up or set-point change
without time limit

After switch-on or after a set-point change, the
alarm output is suppressed , until the process value
is within the limits for the first time.

Relative

g

During alarm configuration, the following functions can be selected

(

ConF / Lim / Fnc.x ):


Function (

Fnc.x)

Remark

Switched off

No limit value monitoring.

Measured value

Process value monitoring. When exceeding the limit, an alarm is
generated.The alarm is reset automatically, when the process
value is "within the limits" (including hysteresis) again.

Measured value + latch Process value monitoring + latching of the alarm condition. When

exceeding the limit value, an alarm is output. A latched alarm
persists, until it is reset manually.