2 parameter, Cntr – West Control Solutions Pro-16 User Manual

Page 53

Advertising
background image

Parameter-Level

9499-040-93811 / 59537-1

Page 53 of 88

Pro-16


Adjustment:

To access the parameter level, press the key

Ù

for 3 seconds and confirm using the

Ù

-key subsequently. If the password function is activated, the prompt for the

PASS is

displayed

The parameters can be adjusted using the

ÌÈ

- keys.

Press the

Ù

- key to change to the next parameter.

After the last parameter of a group,

donE is displayed and followed by automatic

changing to the next group

g

Return to the beginning of a group, by pressing the

Ù

key for 3 sec.

g

Unless a key is pressed during 30 seconds, the controller returns to the process
value and setpoint display (Time Out = 30 sec. )

g

Resetting the configuration parameters to default
r chapter 86 (page 86)


5.2 Parameter

Cntr

Name

Value range

Description

Default

Pb1

1...9999

1 Proportional band 1 (heating) in phys. dimensions (e.g. °C)

100

Pb2

1...9999

1 Proportional band 2 (cooling) in phys. dimensions (e.g. °C)

100

ti1 OFF/0,1...9999 Integral action time 1 (heating) [s]

180

ti2 OFF/0,1...9999 Integral action time 2 (cooling) [s]

180

td1 OFF/0,1...9999 Derivative action time 1 (heating) [s]

180

td2 OFF/0,1...9999 Derivative action time 2 (cooling) [s]

180

t1

0,4...9999 Minimal cycle time 1 (heating) [s]. The minimum impulse is

1/4 x t1

10

t2

0,4...9999 Minimal cycle time 2 (cooling) [s]. The minimum impulse is

1/4 x t2

10

SH

0...9999

Neutral zone or switching differential for on-off control

[phys. dimensions)

2