4 linearization, Functions – West Control Solutions Pro-16 User Manual

Page 74

Advertising
background image

Special

functions

9499-040-93811 / 59537-1

Page 74 of 88

Pro-16

9.4 Linearization

Linearization for input INP1

The "

Lin

" parameter is valid if the following condition is met:

S.tYP and

S.Lin

= 18 (Special linearization)

----

= 23 (KTY11-6)

----

= 30 (Current)

= 1: Special linearization

= 40 (Voltage)

= 1: Special linearization

Dependent of input type, the input signals are specified in μV,

[

, mA or Volt dependent of

input type.

With up to 16 segment points, non-linear signals can be simulated or linearized. Every
segment point comprises an input (

In.1 … In.16) and an output (Ou.1 …

Ou.16). These segment points are interconnected automatically by means of straight
lines.

The straight line between the first two segments is extended downwards and the straight
line between the two largest segments is extended upwards.

I.e. a defined output value is also provided for each input value. When switching an

In.x

value to

OFF, all other ones are switched off. Condition for these configuration

parameters is an ascending order.

In.1

<

In.2

< ...<

In.16

und

Ou.1

<

Ou.2

...<

Ou.16

.