Functions – West Control Solutions Pro-16 User Manual

Page 76

Advertising
background image

Special

functions

9499-040-93811 / 59537-1

Page 76 of 88

Pro-16

Tolerance band

Timer modes 1,2 and 6 are provided with a freely adjustable tolerance band. The tolerance
band around the set-point can be adjusted via parameter

b.ti

in the

Conf

menu

(x =

SP.2

_

b.ti

) (

r page 27).

Timer start

Various procedures for starting the timer are possible:

Start via

LOGI

Mode

Y2

=

SP.2

=

1 2 3 4 5 6

Y / Y2

— switch-over via digital input

1

di1 2 x d d d d d d
di2

3 x d d d d d d

di3 4 x d d d d d d
di4

5 x d d d d d d

SP / SP.2

- switch-over via digital

di1 x 2 w

w

w

w

w

d

input

1

di2

x 3 w

w

w

w

w

d

di3 x 4 w

w

w

w

w

d

di4

x 5 w

w

w

w

w

d

Pressing key

è

and select

Y

6 x d d d d d

w

Power on

0 x d d d d d

w

x 0 w

w

w

w

w

d

Changing

t.ti

(extending operation level)

x x d d d d d d

Serial interface (if provided)

x x d d d d d d

1 when using a digital input, adjust parameter di.Fn = 2 ( ConF/ LOGI) (key function)
x no effect

Signal end

If one of the relays activates after the timer has elapsed, parameter

TimE

= 1 and inverse

action

O.Act

= 1 must be selected for the relevant output

OUT.1

OUT.3

in the

ConF

menu (

r page 32). If direct action is selected, the relevant output signals the active

timer.

9.5.2

Determining the timer run-time

The timer run-time can be determined via parameter

t.SP

in the

PArA

menu. The timer

run-time must be specified in minutes with one digit behind the decimal point (0,1 minutes
= 6 seconds).
Alternatively, the timer run-time can be determined directly at extended operating level (

r

chapter 9.5.3).