Level – West Control Solutions Pro-16 User Manual

Page 28

Advertising
background image

Configuration

level

9499-040-93811 / 59537-1

Page 28 of 88

Pro-16

2

 / Y / Off, or 2-point controller with partial/full load switch-
over

3

2 x PID (3-point and continuous)

4

3-point stepping controller

mAn

Manual operation permitted

0

0 no

1

yes (see also

LOGI/ mAn

)

C.Act

Method of controller operation

0

0

inverse, e.g. heatingWith decreasing process value, the
correcting variable is increased, with increasing process
value, the correcting variable is reduced.

1

direct, e.g. coolingWith increasing process value, the
correcting variable is increased, with decreasing process
value, the correcting variable is decreased

FAIL

Behaviour at sensor break

1

0

controller outputs switched off

1

y = Y2

2

y = mean output. In the event of a failure of the input signal,
the mean value of the correcting variable output last is
kept.The maximum permissible output can be adjusted with
parameter

Ym.H

. To prevent determination of inadmissible

values, mean value formation is only if the control deviation is
lower than parameter

L.Ym

.

3

y = mean output; manual adjustment is possible.In the event of
a failure of the input signal, the mean value of the correcting
variable output last is kept.The maximum permissible output
can be adjusted using parameter

Ym.H

. The mean output is

measured at intervals of 1 min., when the control deviation is
smaller than parameter

L.Ym

.

rnG.L -1999...9999 X0 (lower limit of control range ) indicates the smallest value

to be expected as process value.

-100

rnG.H -1999...9999 X100 (high limit range of control) indicates the highest value

to be expected as process value.

1200

SP2C

With active SP.2 no cooling controlling is provided

0

0

standard (cooling permissible with all set-points)

1

no cooling provided with active SP.2

CYCL

Characteristic for 2-point- and 3-point-controllers

0

0

Standard (see page 42)

1

water cooling linear (see page 43)

2

water cooling non-linear (see page 44)

3

with constant cycle (see page 45)