Special functions, 1 start-up circuit, Functions – West Control Solutions Pro-16 User Manual

Page 71

Advertising
background image

Special

functions

9499-040-93811 / 59537-1

Page 71 of 88

Pro-16

9. Special functions

9.1 Start-up circuit


The start-up circuit is a special function for temperature control, e.g. hot runner control. High-
performance heating cartridges with magnesium oxyde insulation material must be heated
slowly to remove moisture and prevent destruction.
Operating principle:

1

After switching on the supply voltage, stabilised to the start-up set-point

SP.St

is using a maximum start-up correcting value of

Y.St.

2

The start-up holding time

t.St is started one K below the start-up set-point

(

SP.St-1K).

3

Subsequently, the process is lined out to set-point W.

4

If the process value drops by more than 40 K below the start-up set-point
(

SP.St- 40K) due to a disturbance, the start-up procedure is re-started ( 5, 6, 7).

g

With W <

SP.St, W is used as set-point. The start-up holding time t.St is

omitted.

g

If the gradient function (

PArA/ SEtP/ r.SP OFF) was selected, start-up

value

SP.St is reached with the adjusted gradient r.SP.

g

With the boost function (see chapter 9.2 page 72) selected, W is increased by
SP.bo during time t.bo .

The following settings can be selected:
SP.Fn = 10 set-point + start-up circuit

The start-up circuit is effective only with the internal set-point.

SP.Fn = 11 set-point, SP.E /SP.2 + start-up circuit

The start-up circuit is effective also with the external set-point

SP.E and the 2nd set-point SP.2.