Cr1 out select, Cr2 out select, Cr3 out select – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 100: Cr4 out select, Dig out freq, Dig out current, Dig out torque, Dig at temp

Advertising
background image

7–28

Programming

Digital I/O

[CR1 Out Select]

– Stand-Alone Version Only

[CR2 Out Select]

– Stand-Alone Version Only

[CR3 Out Select]

– Stand-Alone Version Only

[CR4 Out Select]

– Stand-Alone Version Only

This parameter sets the condition that changes the state
of the output contacts at TB3-TB4 terminals 10 & 11 (CR1),
11 & 12 (CR2), 13, 14, 15 (CR3) and 16, 17, 18 (CR4).

A change of state may mean energize or de-energize the
relay, since some relays may energize on power-up and
de-energize when the selected condition occurs.

A red LED located on the Main Control Board indicates the
status of the CR3 contact. The LED will illuminate when
the contacts at terminals 13 & 14 of TB3 are closed and
terminals 14 & 15 are open.

Parameter Number

158, 174-176

Parameter Type

Read and Write

Factory Default

“At speed” CR1

“Running” CR2

“Fault” CR3

“Alarm” CR4

Units

Display Drive

“Fault” 0

Any fault

“Alarm” 1

Any unmasked alarm

“Running” 2

Outputting frequency

“At Speed” 3

Output = command

“At Freq” 4

Requires value in [Dig Out Freq]

“At Current” 5

Requires value in [Dig Out Curr]

“At Torque” 6

Requires value in [Dig Out Torque]

“Current Lmt” 7

In overload

“Mtr Overload” 8

At present levels O.L. will occur

“Line Loss” 9

Line loss in progress

“Drive Power” 10 Full input volts present, bus charged

“Drive Ready” 11 All necessary commands present

“Forward Run” 12 Forward direction
“Reverse Run” 13 Reverse direction

“Braking” 14 DC brake mode (stopping or holding)

“Economize” 15 Auto economizer active
“Auto Reset” 16 Attempt to reset fault & restart drive

“At Temp” 17 Requires value in (Dig At Temp]

“PI Max Error” 18 Requires value in [PI Max Error]

“Remote” 19 Set by [Remote CR Output]

Firmware 5.001 & later

“Step Logic” 20 Set by [SLx Step Setting] SL Output

[Dig Out Freq]

– Stand-Alone Version Only

This value sets the trip point for any digital output relay
(CR1-4 – see above) that is programmed to “At
Frequency”. The relay will be energized when the value is
exceeded.

Parameter Number

159

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Hertz / 32767 = Max Freq

Factory Default

0.00 Hz

Minimum Value

0.00 Hz

Maximum Value

Programmed [Maximum Freq]

[Dig Out Current]

– Stand-Alone Version Only

This value sets the trip point for any digital output relay
(CR1-4 – see above) that is programmed to “At Current”.
The relay will be energized when the value is exceeded.

Parameter Number

160

Parameter Type

Read and Write

Display Units / Drive Units

0% / 4096 = 100% of Drive Rated Amps

Factory Default

0 %

Minimum Value

0 %

Maximum Value

200 %

[Dig Out Torque]

– Stand-Alone Version Only

This value sets the trip point for any digital output relay
(CR1-4 – see above) that is programmed to “At Torque”.
The relay will be energized when the value is exceeded.

Parameter Number

161

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Amps / 4096 = Rated Torque Amps

Factory Default

0.0 Amps

Minimum Value

0.0 Amps

Maximum Value

200% of [Rated Amps]

[Dig At Temp]

– Stand-Alone Version Only

This parameter sets the heatsink temperature trip point for
any digital output relay (CR1-4 – see above) that is
programmed to “At Temp.” The relay will be energized
when this value is exceeded. See also [Drive Status 2], bit
13 and [Drive Alarm 1], bit 10.

Parameter Number

267

Parameter Type

Read and Write

Display Units / Drive Units

1

°

C / Deg. C

Factory Default

120

°

C

Minimum Value

0

Maximum Value

255

°

C