Ir drop volts, Flux up time, Start boost – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 129: Run boost, Boost slope, Break voltage, Break frequency
Programming
7–57
[IR Drop Volts]
Used in “Economize” & “Sens Vector” modes - Sets the
value of volts dropped across the resistance of the motor
stator. If set to zero, the drive will use an internal value
based on motor F.L.A. and rated voltage. Some motors
(i.e. 6 pole, special, etc.) may be particularly sensitive to
the adjustment of this parameter. Refer to the tuning
procedure in Chapter 6 for further information.
Parameter Number
194
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Volt / 4096 = Drive Rated Volts
Factory Default
Based on Drive Size & Type
Minimum Value
0.0 Volts
Maximum Value
25% of Drive Rated Volts
[Flux Up Time]
Sets the amount of time the drive will use to try and achieve
full motor stator flux. When a Start command is issued, DC
current at current limit level is used to build stator flux
before accelerating.
Parameter Number
200
Parameter Type
Read and Write
Display Units / Drive Units
0.1 Sec / Sec x 10
Factory Default
0.0 Sec
Minimum Value
0.0 Sec
Maximum Value
5.0 Sec
[Start Boost]
This parameter sets the DC start boost level for
acceleration when [Control Select] is set to “Fixed Boost”
or “Full Custom.”
Parameter Number
48
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
0 Volts
Minimum Value
0 Volts
Maximum Value
9.5% of Drive Rated Voltage
[Run Boost]
This parameter sets the DC boost level for constant speed
level when [Control Select] is set to “Fixed Boost” or “Full
Custom.”
Parameter Number
83
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
0 Volts
Minimum Value
0 Volts
Maximum Value
9.5% of Drive Rated Voltage
[Boost Slope]
Sets the slope of the volts/Hertz curve from [Start Boost]
and [Run Boost] to the intersect point (see Fixed boost
diagram on previous page) when [Control Select] equals
fixed boost. The intersect is determined by multiplying:
Run Boost x Boost Slope = A
Start Boost x Boost Slope = B.
Parameter Number
169
Parameter Type
Read and Write
Display Units / Drive Units
None
Factory Default
1.5
Minimum Value
1.0
Maximum Value
8.0
[Break Voltage]
Sets the voltage the drive will output at [Break Frequency].
Combined with [Break Frequency], this parameter
determines the volts-per-Hertz pattern between 0 and
[Break Frequency].
Parameter Number
50
Parameter Type
Read and Write
Display Units / Drive Units
1 Volt / 4096 = Drive Rtd Volts
Factory Default
25% of Drive Rated Voltage
Minimum Value
0 Volts
Maximum Value
50% of Drive Rated Voltage
[Break Frequency]
This parameter sets a midpoint frequency on a custom
volts-per-Hertz curve. Combined with [Break Voltage], this
value determines the volts-per-Hertz ratio between 0 and
[Break Frequency].
Parameter Number
49
Parameter Type
Read and Write
Display Units / Drive Units
1 Hertz / Hertz x 10
Factory Default
25% of [Maximum Freq]
Minimum Value
0 Hz
Maximum Value
120 Hz