Ir drop volts, Flux up time, Start boost – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 129: Run boost, Boost slope, Break voltage, Break frequency

Advertising
background image

Programming

7–57

Motor Control

[IR Drop Volts]

Used in “Economize” & “Sens Vector” modes - Sets the
value of volts dropped across the resistance of the motor
stator. If set to zero, the drive will use an internal value
based on motor F.L.A. and rated voltage. Some motors
(i.e. 6 pole, special, etc.) may be particularly sensitive to
the adjustment of this parameter. Refer to the tuning
procedure in Chapter 6 for further information.

Parameter Number

194

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Volt / 4096 = Drive Rated Volts

Factory Default

Based on Drive Size & Type

Minimum Value

0.0 Volts

Maximum Value

25% of Drive Rated Volts

[Flux Up Time]

Sets the amount of time the drive will use to try and achieve
full motor stator flux. When a Start command is issued, DC
current at current limit level is used to build stator flux
before accelerating.

Parameter Number

200

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Sec / Sec x 10

Factory Default

0.0 Sec

Minimum Value

0.0 Sec

Maximum Value

5.0 Sec

[Start Boost]

This parameter sets the DC start boost level for
acceleration when [Control Select] is set to “Fixed Boost”
or “Full Custom.”

Parameter Number

48

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

9.5% of Drive Rated Voltage

[Run Boost]

This parameter sets the DC boost level for constant speed
level when [Control Select] is set to “Fixed Boost” or “Full
Custom.”

Parameter Number

83

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

0 Volts

Minimum Value

0 Volts

Maximum Value

9.5% of Drive Rated Voltage

[Boost Slope]

Sets the slope of the volts/Hertz curve from [Start Boost]
and [Run Boost] to the intersect point (see Fixed boost
diagram on previous page) when [Control Select] equals
fixed boost. The intersect is determined by multiplying:
Run Boost x Boost Slope = A
Start Boost x Boost Slope = B.

Parameter Number

169

Parameter Type

Read and Write

Display Units / Drive Units

None

Factory Default

1.5

Minimum Value

1.0

Maximum Value

8.0

[Break Voltage]

Sets the voltage the drive will output at [Break Frequency].
Combined with [Break Frequency], this parameter
determines the volts-per-Hertz pattern between 0 and
[Break Frequency].

Parameter Number

50

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

25% of Drive Rated Voltage

Minimum Value

0 Volts

Maximum Value

50% of Drive Rated Voltage

[Break Frequency]

This parameter sets a midpoint frequency on a custom
volts-per-Hertz curve. Combined with [Break Voltage], this
value determines the volts-per-Hertz ratio between 0 and
[Break Frequency].

Parameter Number

49

Parameter Type

Read and Write

Display Units / Drive Units

1 Hertz / Hertz x 10

Factory Default

25% of [Maximum Freq]

Minimum Value

0 Hz

Maximum Value

120 Hz