Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 42
4–4
Installation/Wiring for PLC Control Drives
Circuits must be capable of operating with high = true logic.
DC external circuits in the low state must generate a voltage of no
more than 8V DC. Leakage current must be less than 1.5 mA into a
2.5k ohm load.
DC external circuits in the high state must generate a voltage of +20
to +26 volts and source a current of approximately 10 mA for each
input. The PLC control version is compatible with these
Allen-Bradley PLC modules:
• 1771-OB
• 1771-OQ16
• 1771-OB16
• 1771-OBD
• 1771-OYL
• 1771-OBN
• 1771-OZL
• 1771-OQ
• 1771-OBB
The 24 volt power supply is capable of supplying a total of 16 digital
inputs.
Typical
20
21
22
23
24
25
0.22
µ
f
1k
20k
510
510
510
TB5
TB7
24V Common
24V
1
Only used if 3-Wire Input Mode selected
1
1
Contacts shown are general, refer to Input Mode Select and information presented above.