3–8

Installation/Wiring for Stand-Alone Drives

Pulse Input/Output Option

Pulse Input

The pulse input signal must be an externally powered square-wave
pulse at a 5V TTL logic level. As measured at the terminal block,
circuits in the high state must generate a voltage between 3.6 and
5.5V DC at 8 mA. Circuits in the low state must generate a voltage
between 0.0 and 0.8V DC. Maximum input frequency is 250kHz.
Scale factor [Pulse/Enc Scale] must be set.

Pulse Output

Provides a TTL pulse train suitable for driving up to three
1336 SPIDER pulse inputs or a separate 125 ohm load at TTL levels
(4V at 32 mA source, 0.8V at 3.2 mA sink).

Important: An LA5 Analog Option must be installed to use the pulse

input/output options. See Figure 3.4 for terminal
designations.

Digital Outputs

The digital outputs are at terminals 10 through 18 of TB3-TB4.

Figure 3.3
Digital Outputs

!

ATTENTION: If input voltages are maintained at levels
above

±

15V DC, signals may be degraded and component

damage may result.

CR2

CR1

CR3

CR3

CR4

CR4

Terminal
10, 11
11, 12
13, 14
14, 15
16, 17
17, 18

Signal
CR1 Programmable Contact
CR2 Programmable Contact

CR3 Programmable Contact

CR4 Programmable Contact

Resistive Rating = 115V AC/30V DC, 5.0A
Inductive Rating = 115V AC/30V DC, 2.0A

Contacts Shown

in Unpowered State

(or powered state with

fault/alarm present)

Important: The power supply used for relay contact outputs requires a field installation

of transient voltage surge suppression with maximum clamping voltage of
2.5 kV on all control boards.

10

11

12

13

14

15

Output 1

Common

Output 2

Output 3

Common

Output 4

17

TB4

18

Common

Output 6

16

Output 5

TB3