Owners, Stop owner, Direction owner – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 117: Start owner, Jog owner, Reference owner, Accel owner

Advertising
background image

Programming

7–45

Owners

This group of parameters contains binary information to display which group of adapters
are issuing control commands.

Each Owner Parameter contains a bit for each adapter.
The drive will set an adapter’s bit to “1” when that adapter
is issuing a logic command and to “Zero” when no
command is being issued.

A Status description (bit ENUM) is displayed on line 1
(except Series A HIMs below version 3.0).

[Stop Owner]

This parameter displays which adapters are presently
issuing a valid stop command.

Parameter Number

102

Parameter Type

Read Only

Units

Display Drive

“0” 0

Stop Input Not Present

“1” 1

Stop Input Present

[Direction Owner]

This parameter displays which adapter currently has
exclusive control of direction changes.

If [Freq Select 1] or [Freq Select 2] is set to “Analog In 0”
and an Analog Option Board with bipolar input (LA6, LA7)
is installed, that input (designated “Analog In 0”) will have
exclusive ownership of direction. Bit 7 of [Direction Mask]
must not be set to “0” and no other device can have claimed
ownership of direction (i.e. TB5 - Run Reverse). If either
condition is true, a fault will be issued.

Parameter Number

103

Parameter Type

Read Only

Units

Display Drive

“0” 0

Non-Owner

“1” 1

Current Owner

[Start Owner]

This parameter displays which adapters are presently
issuing a valid start command.

Parameter Number

104

Parameter Type

Read Only

Units

Display Drive

“0” 0

Start Input Not Present

“1” 1

Start Input Present

[Jog Owner]

This parameter displays which adapters are presently
issuing a valid jog command.

Parameter Number

105

Parameter Type

Read Only

Units

Display Drive

“0” 0

Jog Input Not Present

“1” 1

Jog Input Present

[Reference Owner]

This parameter displays which adapter currently has the
exclusive control of the selection of the command
frequency source.

Parameter Number

106

Parameter Type

Read Only

Units

Display Drive

“0” 0

Non-Owner

“1” 1

Current Owner

[Accel Owner]

This parameter displays which adapter has exclusive
control of selecting [Accel Time 1] or [Accel Time 2].

Parameter Number

107

Parameter Type

Read Only

Units

Display Drive

“0” 0

Non-Owner

“1” 1

Current Owner

TB4-TB6
Adapter 1
Adapter 2
Adapter 3
Adapter 4
Adapter 5
Adapter 6
Not Used

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Owners Display

Advertising